Low Freqeuncy Online 30kVA UPS
Product Description:
AR Series Online UPS for Industry 10KVA ~ 200KVA
Model: 10KVA ~ 200KVA
Input AC Voltage: AC380V/400V/415V/480V, 3P3W or 3P4W
Input DC Voltage: DC348V
Input Frequency: 50Hz/60Hz± 10%
Output AC Voltage: AC380V/400V/415V/480V 3P3W or 3P4W, AC220V/230V/240V/277V 1P2W
Output Frequency: 50Hz/60Hz± 0.1%
Features & Advantages:
1. Adopting output isolated, on-line double coversion technology and advanced DSP technology. It is a full digital and intelligent new generation UPS
2. IGBT components with PFC function.
The input power factor is more than 0.985. Effectively reduce the input harmonic and reactive power loss, a really energy efficient UPS for industry.
3. Friendly, full intelligent touch type man-machine interface design to use a 7 inch color LCD display.
It is informative and easy to operate. Easy to perform and modify the initial preset of UPS,
It can adapt to the power supply standards of various countries around the world, supports multi language interface conversion.
4. Ultra-strong overload ability and adopting the technology of five-section overload protection. It is suitable for harsh industrial loads and compatible with the hardware and software
5. The efficiency of the machine is more than 94%, therefore reduce the energy consumption.
6. Adopting negative power detection and anti reverse connection technology, IGBT anti common circuit circulation detection and protection technology which greatly improve the reliability of the system.
7. The key PCBs with conformal coating to protect against the moisture, salt mist and mildew, therefore can withstand the harsh environment of high contamination and high pollution.
8. Advanced and Intelligent battery management system
(1). Exclusively adopting the 3iBMSTM battery wisdom third-order management system which can be preset to a regular test of the battery charge and discharge and with temperature compensation function, thus simplify the battery maintenance procedure, extend the battery life and reduce the battery replacement cost.
(2). With the unique function of automaticlly correct the discharge cut-off voltage of the battery low discharging current to avoid the battery deep discharge resulted in a permanent damage to battery
(3). With the Intelligent battery connection detection and battery reverse connection protection. Therefore any connection mistake and power on/off in a wrong order will cause no harm to the battery.
9. Intelligent Fan Rotation Speed Control with the fault diagnosis function and the redundancy design
The fan rotation speed can change automatically according to the load capacity and the actual temperature, thus improve the system reliability and greatly reduce the audible noise.
10. Plug & Play Module Design Plug & Play Module Design to allow for quick maintenance and troubleshotting.
11. Dry Contacts, RS-232/ RS485 (MODBUS) as standard configuration, SNMP card and remote control panel are available for option.
12. History Data Record Ability
The unlimited quantity of the history data can be stored, can be downloaded to U disk. Therefore the user can analyse the operation status of the UPS.
13. Compatibility design, custom-made non-standard UPS, reserved interface for parellet redundancy with multi-units
Back Panel Description:
We will always support you if you need any
assistant!
Model | L10K3/3 | L20K3/3 | L30K3/3 | L40K3/3 | L60K3/3 | L80K3/3 | L100K3/3 | L120K3/3 | L160K3/3 | L200K3/3 | L300K3/3 | L400K3/3 |
Nominal capacity(KVA) | 10KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | 120KVA | 160KVA | 200KVA | 300KVA | 400KVA |
Work principle | Pure sine wave online |
Phase | 3 phase +N+G |
Input power factor | >0.8, >0.95 |
Rectifier | Nominal input voltage | 220/380VAC, 230/400VAC, 240/415VAC |
Range | ±25% |
Nominal input frequency | 50Hz±10%, 60Hz±10% |
Output ripple | < 2 % |
Soft start | 0 ~ 100% 5s |
Charge | Charge mode | Constant current to constant voltage, with temp compensation; with auto change |
Float voltage | 432VDC |
Boost voltage | 464VDC |
Temperature compensation voltage | 3mV/°C(monomer) |
Charge current | 0.1C ( automatically change according to battery capacity ) |
Charge power | 20 % of rated capacity |
Battery | Battery type | Maintenance-free lead acid battery |
Battery capacity | 7 ~ 999AH settable(according to the capacity) |
Battery number | 32pcs 12V, or 192pcs 2V ( nominal voltage 384VDC ) |
Inverter | Phase | 3 phase +N |
Rated power | Rated capacity×0.8 |
Nominal voltage | 220/380VAC, 230/400VAC, 240/415VAC |
Output voltage stability | ±1%(stable load); ±3%(fluctuant load) |
Output frequency stability | 50Hz/60Hz < ±0. 5% |
Crest factor | > 3:1 |
Output waveform distortion | Pure sine wave, linear load<3%;non-linear load<5% |
Dynamic characteristics | Instant voltage<±5%(from 0 to100%), instant recover time<10ms |
Unbalanced load voltage | < ±5% |
Overload protection | 125% 1 minute; 150% 1s; 200 % 200ms |
Efficiency | >95 % (full load) |
Bypass | Phase | 3 phase +N |
Nominal voltage | 220/380VAC, 230/400VAC, 240/415VAC |
Transfer time | <1ms(static switch with 0 transfer time) |
Protection | Input protection | Input voltage/frequency over limited; wrong phase; lack phase protection |
Output protection | Over current; short circuit; factor low protection |
Battery protection | Over charge; over-discharge protection |
Temperature protection | Environment over temperature protection; inverter over temperature protection |
Hardware failure protection | Assistant power abnormal, breaker cut off, breaker overload, power devices over current/over voltage etc. protection |
System parameters | Working environment | Temp: 0 ~ 40°C , relative humidity 30% ~ 90 % (1% decrease against 100 meters' rise, altitude 4000 meters Max) |
Cooling down method | Compulsive ventilation(with temperature control) |
Communication interface | RS232, RS485; optional SNMP card(for internet long distance monitor) |
Redundancy function | Tandem hot backup or parallel connection |
Anti-surge capacity | 10/700μS, 5KV; 8/20μS, 20KA |
Protection level | IP21 |
Safety performance | Vin-n Vout-n 3000VAC, creepage<3.5mA, insulating resistance>2M Ω (500VDC) |
Noise(dB) | 40~50 | 45-55 | 55~60 | 60~65 | 65 ~ 70 |
Dimension(W×D×H)mm | 430×750×1080 | 480×895×1200 | 980×800×1800 | 1380×950×1800 | 1600×1150×1800 |
Weight(Kg) | 200 | 350 | 400 | 480 | 580 | 850 | 920 | 1200 | 1300 |